www.stiebel-eltron.com WPM 3| 41
INSTALLATION
Commissioning
Menu item Options Unit Min. Max. Standard System value
Settings / heating / standard setting
BUFFER OPERATION ON / OFF ON / OFF
SUMMER MODE ON / OFF ON
OUTSIDE TEMPERATURE °C 3 30 20
BUILDING HEAT BUFFER 0 3 1
FLOW PROP HEATING CIRC % 0 100
MAXIMUM RETURN TEMP °C 20 65 65
MAXIMUM FLOW TEMPERATURE °C 20 75 75
FIXED VALUE OPERATION OFF °C 20 70 OFF
HEATING CIRCUIT OPTIMAL OFF 0.01 0.1
FROST PROTECTION °C -10 10 4
Settings / heating / remote control FE7
HEATING CIRC PRESELECTION Heating circuit 1
Heating circuit 2
Heating circuit 1
ROOM INFLUENCE OFF 0 20 5
ROOM CORRECTION K -5 5 0
Settings / heating / pump cycles
PUMP CYCLES ON / OFF ON / OFF OFF
Settings / Heating / External heat source
THREADED IMMERSION HEATER ON / OFF
BOILER ON / OFF
HZG PWM ON / OFF
HEATING CURVE GAP K 1 15 3
SET BOILER TEMPERATURE °C 35 90
BLOCKING TIME EVU OFF h 1 10
LOWER APP LIMIT HZG OFF °C -19.5 40 -20
DUAL MODE TEMP HZG °C -20 40 -20
HZG PWM Kmin 10 100
Settings / heating / electric reheating
LOWER APP LIMIT HZG OFF °C -20 40 -20
DUAL MODE TEMP HZG °C -20 40 -20
NUMBER OF STAGES 0 3 3
DELAY OFF min 1 60 60
Settings / DHW / DHW temperatures
COMFORT TEMPERATURE °C 10 60 50
ECO TEMPERATURE °C 10 60 50
Settings / DHW / standard setting
PRIORITY OPERATION ON / OFF ON
PARALLEL OPERATION ON / OFF OFF
PARTIAL PRIORITY ON / OFF OFF
DHW HYSTERESIS K 1 10 5
DHW STAGES 1 6 1
AUTOMATIC DHW CONTROL ON / OFF OFF
OUTSIDE TEMPERATURE °C -5 30
WW LEARNING FUNCTION ON / OFF OFF
WW CORRECTION 0 5
COMBI CYLINDER ON / OFF OFF
WW OUTPUT SUMMER kW 5 15 5
WW OUTPUT WINTER kW 5 15 5
MAXIMUM FLOW TEMPERATURE °C 20 75 75
PASTEURISATION ON / OFF OFF
Settings / DHW / electric reheating
DUAL MODE TEMP WW °C -20 40 -20
LOWER APP LIMIT WW OFF °C -20 40 -20