42 | WPM 3 www.stiebel-eltron.com
INSTALLATION
Commissioning
Menu item Options Unit Min. Max. Standard System value
Settings / DHW / External heat source
SUPPORTED ON / OFF
ALONE ON / OFF
INDEPENDENT ON / OFF
DUAL MODE TEMP WW °C -20 40 -20
LOWER APP LIMIT WW OFF °C -19.5 40 -20
WW PWM % 0 100
Settings / cooling
COOLING ON / OFF OFF
SETTINGS / COOLING / COOLING MODE
PASSIVE COOLING ON / OFF OFF
ACTIVE COOLING ON / OFF OFF
SETTINGS / COOLING / STANDARD SETTING
COOLING STAGES 1 6 6
COOLING LIMIT °C 15 40 20
COOLING CAPACITY kW 3 10 8
SETTINGS / COOLING / ACTIVE COOLING / AREA COOLING
SET FLOW TEMPERATURE °C 7 25 15
FLOW TEMP HYSTERESIS K 1 5 5
SET ROOM TEMPERATURE °C 20 30 25
DYNAMICS ACTIVE 1 10 10
DYNAMICS PASSIVE 0 10
Settings / cooling / active cooling / fan cooling
SET FLOW TEMPERATURE °C 7 25 15
FLOW TEMP HYSTERESIS K 1 5 5
SET ROOM TEMPERATURE °C 20 30 25
DYNAMICS ACTIVE 1 10 10
DYNAMICS PASSIVE 0 10
Settings / cooling / passive cooling / AREA COOLING
SET FLOW TEMPERATURE °C 7 25 15
FLOW TEMP HYSTERESIS K 3 10 5
SET ROOM TEMPERATURE °C 20 30 25
DYNAMICS PASSIVE 1 10
Settings / cooling / passive cooling / fan cooling
SET FLOW TEMPERATURE °C 7 25 15
FLOW TEMP HYSTERESIS K 3 10 5
SET ROOM TEMPERATURE °C 20 30 25
DYNAMICS PASSIVE 1 10
Settings / SOLAR
MAXIMUM CYLINDER TEMP °C 20 85
SOLAR DIFFERENTIAL K 3 11
Commissioning
ENTER CODE 0000 9999 1000
LANGUAGE English
Commissioning / Source
MIN SOURCE TEMPERATURE OFF °C -10 10 -9
BRINE PUMP RATE % 20 100
Commissioning / Heating
CONTROLLER DYNAMICS 1 600 100
HYSTERESIS K 1 10 1
HD SENSOR MAX bar 38 44
SPREAD CONTROL ON / OFF
SET SPREAD K 3 12 5