Chapter 6 Operation
www.supmea.com
-38-
coefficient is greater than 1 , then increase the flow velocity ; if the
correction coefficient is less than 1 , then decrease the flow velocity ;
1-11
Flow
correction
point 1
Figure
Manufacturer
0.0-99.999
0
Flow rate modified point 1, when The flow rate function shut down , this
parameter does not display.
1-12
Flow
correction
coefficient 1
Figure
Manufacture
0.0-99.999
1.000
Flow rate correction factor 1, when The flow rate function is disabled,
this parameter does not display.
1-13
Flow
correction
point 2
Figure
Manufacturer
0.0-99.999
0
Flow rate modified point 2, when The flow rate function is disabled, this
parameter does not display.
1-14
Flow
correction
coefficient 2
Figure
Manufacture
0.0-99.999
1.000
Flow correction factor 2. This parameter is not displayed when the flow
function is off.
1-15
Flow
correction
coefficient 3
Figure
Manufacturer
0.0-99.999
0
Flow rate modified point 3, when The flow rate function is disabled, this
parameter does not display.
1-16
Flow
correction
coefficient 3
Figure
Manufacturer
0.0-99.999
1.000
Flow rate modified point 3, when The flow rate function is disabled, this
parameter does not display.
1-17
Flow
correction
coefficient 4
Figure
Manufacturer
0.0-99.999
0
Flow rate modified point 4, when The flow rate function is disabled, this
parameter does not display.
1-18
Flow
Figure
Manufacturer
0.0-99.999
1.000