Chapter 6 Operation
www.supmea.com
Used for check and modify parameter configuration;
When the manufacturer’s password is entered, this parameter is not
displayed. Ex-factory password: 200000
Threshold for empty tube alarm judgment
Actual
electrical
conductivity
Display the measured conductivity equivalent of the fluid.
For general natural water: equivalent < 200 when the tube is full,
equivalent > 1200 when the tube is empty ( the equivalent is related to
the fluid conductivity and the length of measuring line, it is recommended
to use double shielded wire when the wiring distance is 20m , otherwise it
will affect empty detection function.)
Empty pipe
check
permission
Set whether to enable empty detection function
Measured conductivity equivalent value when the tube is empty, default
values can be used for general natural water. It needs to observe
whether the empty pipe for special fluid is that displayed as 9-1, then
record it in 9-3.
Measured conductivity equivalent value when the tube is full, default
values can
be used for general natural water. It needs to observe whether the empty
pipe for special fluid is that displayed as 9-1, then record it in 9-4.