Technical Data
6-2
Lines 20 20 20
Characters/Line 40 40 40
Display Area (H x W) 90 mm x 120 mm
(3.543" x 4.724")
90 mm x 120 mm
(3.543" x 4.724")
90 mm x 120 mm
(3.543" x 4.724")
Display TP22EM TP22ES TP22ET
Electrical Data
Supply Voltage 24 V DC (SELV in Accordance with DIN EN 61131)
Residual Ripple 10% Maximum
Minimum Voltage 19.2 V
Maximum Voltage 30.2 V
Power Consumption (Field Bus Device) TP22EM / TP22ES: 0.4 A
TP22ET: 0.5 A
Connected Load TP22EM / TP22ES: 10 W
TP22ET: 12 W
Fuse Semiconductor Fuse, Self-resetting
Protection Against Polarity Reversal Integrated
Standard Interfaces
Variable Baud Rates and Data Formats
X3 SER1 TTY / 20 mA According to CL 2 and DIN 66 348 T1
Transmission Length: 0 - 1000 m (3280.84 ft.), Twisted Pair,
Shielded
Electrically Isolated
X3 SER1 RS485 According to DIN 66259-4
Transmission Length: 0 - 1200 m (3937.01 ft.), Twisted Pair,
Shielded
Electrically Isolated
X3 SER1 RS232c / X3 SER2 RS232c According to DIN 66259 T1, CCITT V.28
Transmission Length: 0 - 15 m (49.21 ft.), Layer-stranded,
Shielded
X3 SER1: Electrically Isolated
X3 SER2: Not Electrically Isolated
Field Bus Interfaces
Variable Baud Rates and Data Formats
X2.1 / X2.2 CAN Bus According to ISO 11898
Electrically Isolated
X2.1 / X2.2 DeviceNet According to ISO 11898
Electrically Isolated