First, set F0-01 as 0: the control mode selection is the operating panel command channel.
Set F1-00 as 0 by actual motor types: asynchronous motor. Then set F1-01、F1-02、F1-03、
F1-04、F1-05 according to the nameplate parameters of motor.
If the motor can be separated from load, the parameter F1-11 selects 2(motor no-load tuning).
Then press RUN of the operating panel and the motor can automatically run.
The control
automatically counts these parameters as follows: F1-06 (stator resistance), F1-07 (rotor
resistance), F1-08 (leakage inductance), F1-09 (mutual inductance) and F1-10 (no-load
excitation current). The motor tuning is then over. If the system appears over current, please
increase the parameter F1-10, but don’t exceed 20%.
If the motor can’t be separated from load, the parameter F1-11 se
lects 1(motor with-load
tuning).Then press RUN of the operating panel and the motor can automatically tune. The
controller only automatically counts three parameters: stator resistance, rotor resistance, and
leakage inductance. It automatically counts mutual inductance and no-load current of motor as
well.