NICE3000 User Manual Function parameter description
141
FB-03
Front door service oor 2 Default 65535 Min. Unit 1
Setting Range 065535set 1731 oor
This function code is made up of binary numbers with 16 emic that control those oors allowing
front door to open normally within floor 17 to floor 31. Every floor door is controlled by one
binary number.
1Relevant oors front door can be open.
0Forbidden relevant oors front door open.
Its setting way is
the same with F6-05; details are shown in section 6.7.
FB-04
Back door service oor 1 Default 65535 Min. Unit 1
Setting Range 065535set 116 oor
This function code is made up of binary numbers with 16 emic that control those oors allowing
back door to open normally within oor 1 to oor 16. Every oor door is controlled by one binary
number.
1Relevant oors back door can be open.
0Forbidden relevant oors back door open.
Its setting way is the same
with F6-05; details are shown in section 6.7. The function parameter
can only be valid when the door number of FB-01 is 2.
FB-05
Back door service oor 2 Default 65535 Min. Unit 1
Setting Range 065535set oor 1731
This function code is made up of binary numbers with 16 emic that control those oors allowing
back door to open normally within oor 17 to oor 31. Every oor door is controlled by one
binary number.
1Relevant oors back door can open.
0Forbidden relevant oors back door open.
Its setting way is the same w
ith F6-05; details are shown in section 6.7. The function parameter
can only be valid when the door number of FB-01 is 2.
FB-06
Open door time protection Default 10s Min. Unit 1s
Setting Range 599s
FB-08
Close door time protection Default 15s Min. Unit 1s
Setting Range 599s
The open/close door time protection means: When the system outputs open/close door
command but doesnt receive open/close door limit feedback after the time of FB-06, the
door machine turns to close/open door at once. This is once for door open and close. When
it reaches the times FB-09 (open/close door times) setting of open/close door, the system will
warn E48 door open error or E 49 door close error.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Suzhou Monarch Control Technology MCTC-GCB-A and is the answer not in the manual?

Suzhou Monarch Control Technology MCTC-GCB-A Specifications

General IconGeneral
BrandSuzhou Monarch Control Technology
ModelMCTC-GCB-A
CategoryController
LanguageEnglish

Related product manuals