NICE3000 User Manual System typical application and adjustment
159
Put 100% rated load into the car. Adjust the switch position of full load to make full load

switch act but over load switch not. The system memorizes it as full load.
Put 110% rated load into the car. Adjust the switch position of over load. to make over

load switch act. The system memorizes it as over load.
When complete upwards work, lift can be ready to run at high speed.
Test at high speed4)
Car command testinga)
Let the lift in self-motion state. Key in signal level command by shortcut key F1 in small
keyboard or function code F7-00 in special control panel. Observe whether the lift runs
according to setting command or not.
External call command testingb)
Let the lift in self-motion state. Key in external call up and down command by function code
F7-01, F7-02 in special control panel
, or press every oor external call. Observe whether the lift
runs according to setting command or not.
Door open and close function testingc)
When the lift stop at the landing, observe whether the door opens normally or not and whether
doors keeping time meets the requirements or not. When lift responds to call and be to run,
observe whether the door close normally or not.
Fast speed running5)
Aft
er testing at high speed, stop lift and add required functions. Then start adjusting at high
speed.
Set FE-32, FE-33 and F8-08 according to users actual needs.a)
According to user and actual needs, adjust F6 group parameters; Set service oor, lock b)
main landing F6-04, re main landing F6-03, parking main landing F6-02, and group
control, time-sharing control, parallel fastigium control.
Function
test of re return to main landingc)
If there is the re return to main landing function availability and the re main landing is setting,
dial the re button in the re landing. Then observe whether the lift can return to the re landing
normally and the door state meets the requirements.
Firemen run functiond)
If there is fireman running function setting, after the lifts fire returns to the mai
n landing,
dial the re button and the lift immediately gets into the reman running state. The lift wont
respond to the external call, and the door machine can only open the door when keep pressing
on the open button. Once release the open button, the door close immediately.
Re-leveling function testinge)
If the re-leveling function is availability, observe whether the lift can re-level or not an
d the
re-leveling speed meets the requirements or not. If error is over large, please adjust F3-10
appropriately.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Suzhou Monarch Control Technology MCTC-GCB-A and is the answer not in the manual?

Suzhou Monarch Control Technology MCTC-GCB-A Specifications

General IconGeneral
BrandSuzhou Monarch Control Technology
ModelMCTC-GCB-A
CategoryController
LanguageEnglish

Related product manuals