Function Factory-preset value Adjusted value
Temperature
Temp. Reg. (Control) function X ERS 1 ERS 2 SA EA ERS 1 ERS 2 SA EA
Difference SA/EA (°C) 3,0
Step 2
Breakpoint (°C) 22,0
X1 15,0
Y1 20.0
X2 20.0
Y2 18.0
X3 22.0
Y3 14.0
Setpoint (°C) 21.5 21.5
Min. SA temp. (°C) 15.0
Min. SA temp. (°C) 28.0
Outdoor temp. compensation
X Inactive Active Inactive Active
Temperature
Winter comp. Y1 (°C) 3.0
End point, winter X1 (°C) -20.0
Starting point, winter X2 (°C) 10.0
Startpoint summer X3 (°C) 25.0
Endpoint summer X4 (°C) 40.0
Summer comp. Y2 (°C) 2.0
Summer night cooling
X Inactive Active Inactive Active
EA temp. start (°C) 22.0
EA temp. stop (°C) 16.0
Outdoor air temp. stop (°C) 10.0
SA Setpoint (°C) 10.0
In-oper. time start (hh:mm) 23:00
In-oper. stop (hh:mm) 06:00
Intermittent night-time heating
X Inactive Active Inactive Active
EA/Room start (°C) 16.0
EA/Room stop (°C) 18.0
SA Night setpoint (°C) 28.0
SA flow (m²/s / Pa)
2)
SA flow (m²/s / Pa) 0.0
Damper output =0
Morning BOOST
Time (hh:mm) 00:00
Damper
X Inactive Active Inactive Active
EA fan
X Inactive Active Inactive Active
EA/Room temp 22.0°C
EA min 15.0°C
SA max 28.0°C
Set point displacement
X Inactive Active Inactive Active
External sensor
External EA/Room
X Inactive IQnom Comm. Inactive IQnom Comm.
External outdoor
X Inactive IQnom Comm. Inactive IQnom Comm.