GB.GOLDLP.170830
www.swegon.com 65
We reserve the right to alter specifications without notice.
Function Factory-preset value Adjusted value
Alarm setting
Fire alarm function
Internal fire alarms
X Inactive Active Inactive Active
External fire alarm Alarm resetting
X Man. Auto Man. Auto
Fan oper. in the event of a fire X Inactive SA EA SA+EA Inactive SA EA SA+EA
SA fan speed in event of fire (%) 100
EA fan speed in event of fire (%) 100
External alarms
Time delay Alarm 1 (s) 10
Alarm on closure, Alarm 1 1
Alarm reset
X Man. Auto Man. Auto
Time delay Alarm 2 (s) 10
Alarm on closure, Alarm 2 1
Alarm reset
X Man. Auto Man. Auto
Alarm limit temperature
Deviation, SA setpoint 5,0
Min. EA temperature 15,0
Filter function
Filter alarm limit
SA (%/Pa) 10/100
EA (%/Pa) 10/100
H EXCH defrosting
Alarm limit (Pa) 50
Service period
Alarm limit (month) 12
Alarm priority See the following pages -
Hand-held micro terminal settings
Language English
Flow unit
l/s X m
3
/s m
3
/h l/s m
3
/s m
3
/h
Min./max. setting
Setpoint, SA/EA (°C) 15,0/40,0
Min. limit, SA (°C) 13,0/18,0
Max. limit, SA (°C) 25,0/45,0
Break point, ERS Regulation (°C) 15,0/23,0
SA/EA Difference (°C) 1,0/5,0
Initial setting –
Communication
EIA-485
Protocol Modbus RTU
Address 1
PLA (Exoline) 1
ELA (Exoline) 1
Speed 9600
Parity None
Stop bit 1