14
| Installation
Table 7 AXCBF Type key
AXCBF 500– D2 20° IE2
Axial fan bifurcated Nominal diameter of
the fan
3-phase motor 2–
pole
Blade angle International
efficiency
Table 8 IV Type key
IV 50– 4
-
Induction fan Thrust 50N Number of poles
Temperature- Time
information (smoke
extraction fan), see 5.1.5
Temperature types, page 5
7 Installation
7.1 Safety information
Danger: Risk that the fan does not work in case of fire.
Spring vibration mounts made from unsuitable materials do not fulfil their function! For smoke extraction fans (K),
(B) and (F) only use spring vibration mounts made of steel!
Use installation material with fire resistance classes that meet temperature requirements.
Warning: Danger from falling fan or fan parts.
Check the surface before installation for load bearing capacity.
Consider all static and dynamic loads when selecting hoisting equipment and fastening components.
Tighten all screw-type connections according to the data, see Table 9 Tightening torques according to DIN 13, page
15.
General safety information
Installation may only be carried out by adequately qualified persons, details see Table 1 Qualifications, page 2.
Wear protective equipment during all work in the vicinity of the fan, details see 2.2 Personal protective equipment,
page 2.
Abide by the system-related conditions and requirements of the system manufacturer or plant constructor.
Safety elements may not be dismantled, circumvented or deactivated.
Move the impeller of the fan by hand before you install it in order to check whether that moves freely.
Provide the fan at least with an IP 20 protective grille, if the fan is not installed in a duct system.
Prevent the possibility of foreign bodies being drawn in.
To reduce transmission of vibration to the duct system, we recommend flexible connections from our accessory
range, see 5.2.4 Accessories, page 8.
Bear in mind that parts of the impeller may protrude out of the fan housing.
7.2 Preconditions
Ensure that the fan and all its components are undamaged.
Ensure that the information on the name plates (fan and motor) matches up with the operating conditions.
Ensure that there is enough space to install the fan.
Protect against dust and moisture when installing.
Fit the fans in such a way that there is sufficient access for troubleshooting, maintenance and repair.
| 003

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir AXC Series and is the answer not in the manual?

SystemAir AXC Series Specifications

General IconGeneral
BrandSystemAir
ModelAXC Series
CategoryFan
LanguageEnglish

Related product manuals