TAC 2112, Manual Day-to-day Usage
TAC AB, 1999-08-01 0-004-7459-3, 4:1(6)
4 Day-to-day Usage
4.1 Introduction
This chapter provides sufficient information for you to read off and
set temperatures and other parameters during normal operation.
All parameters and functions are described in detail in Chapter 7,
“Functional description”.
4.2 Reading temperatures
Procedure for reading a temperature:
1
2
3
4
5
6
7 8 9 10 11 12 13 14 15 16 17
18
0
23
22
21
20
19
24
K1
P 01
14.7
°C
1 Select parameter number (P No.) by pressing
or as
shown in the list below. Increase or decrease the number by
pressing
or .
2 Hold down the button for fast increase/decrease.
3 Press
and at the same time to get to P 15 – P 99.
4 Read the value.
Temperature P No.
Outdoor temperature P 01
Damped outdoor temperature P 02
Supply temperature P 03
Supply temperature, calculated setpoint P 04
Room temperature P 07
Room temperature, calculated setpoint P 08
Return temperature, heating circuit P 13