EasyManua.ls Logo

TAC 2112 - Reduced Daytime Operation (Optimised Stop)

TAC 2112
70 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TAC 2112, Manual Functional Description
7:16 (22), 0-004-7459-3 (GB) 1999-08-01, TAC AB
7.3.12 Reduced daytime operation (optimised stop)
In systems with a reference sensor, the controller can determine
whether a transition to night operation can take place earlier than the
time set. The controller calculates a new transition time on the basis
of the deviation in room temperature.
The curve below is used when calculating reduced daytime operation.
10
30
-10 0 5-5 10 15 20-15 25-20-25
P 41
y1
(minutes)
of excess temperature
y0
P 42
O
ptimisation time per de
g
ree
Damped
in the room
Curve for reduced daytime operation
The time by which daytime operation is reduced is calculated as:
t = (y-value from curve) • (room temperature + dead zone room - setpoint room)
Example
Setpoint room=20
°
C
Dead zone room=1
°
C
Room temperature=21
°
C
Damped outdoor temperature=10
°
C
The above results in an excess temperature in the room of
21+1–20=2
°
C. The y-value of the curve at +10
°
C is 30 minutes,
which gives an optimisation time of 60 minutes (2 × 30).
The function for reduced daytime operation is blocked when the
equipment is delivered by setting the stop times in the curve to
0 minutes.
Parameters
P No. Parameter Min. Max. Step Default Comments
P 41 Opt. time at –10°C (y0) 0 min. 240 min. 1 min. 0 min.
P 42 Opt. time at +10°C (y1) 0 min. 240 min. 1 min. 0 min.

Related product manuals