TAC 2112, Manual Functional Description
7:8 (22), 0-004-7459-3 (GB) 1999-08-01, TAC AB
Criteria for automatic curve adjustment
The following criteria must be met for the automatic curve adjustment
to work:
A reference sensor is installed.
Automatic curve adjustment is on (P 27).
The controller is working under timed operation.
Daytime operation is on.
The pump is working, i.e. there is a heating requirement.
The return temperature limitation is not active.
Parameters
P No. Parameter Min. Max. Step Default Comments
P 27 Automatic curve adjustment 0 (off) 1 (on) 1 1 (on) With reference sensor only
P 28 I time for curve adj. controller 1 min. 720 min. 1 min. 180 min. With reference sensor only
P 29 Max curve adjustment 0 °C 40 °C 1 °C 5 °C With reference sensor only
7.3.5 Supply controller
Controller
The supply temperature is controlled by a PI controller (proportional
and integrating controller) of the “increase/decrease” type. The
setpoint for this controller is calculated on the basis of the following
parameters:
Operating mode
The reset curve for outdoor temperature compensation
Room temperature effect, if a reference sensor is fitted
Parallel shifting of the reset curve, if no reference sensor is fitted
Return temperature limitation
Remote setpoint control, SPC adjustment
Pump control
Night setback
Supplement during morning boost