TAC 2112, Manual Troubleshooting
6:2(
2
), 0-004-7459-3 (GB) 1999-08-01, TAC AB
Problem Check (that) ...
The calculated setpoint does
not seem to be correct
the effect from the remote heating
control (SPC, P 80) is reasonable
The pump is not running if the pump has stopped due to a
high outdoor temperature or a low
supply temperature (see chapter 7)
The heating is not affected by
the remote control signal
(SPC)
the parameter SPC effect at +10 V
(P 81) is set correctly (see chapter 7)
No night setback occurs the controller is in “timed operation”
or “fixed night setback” mode (see
chapter 7)
the weekly program is set correctly
(see chapter 7)
the parameters for night setback are
set correctly (see chapter 4). If the
outdoor temperature is less than the
limit for 0% night setback, night
setback will not occur.