TAC 2112, Manual Commissioning Protocol / List of Parameters
A:2 (6), 0-004-7459-3 (GB) 1999-08-01, TAC AB
P No. Parameter Min. Max. Step Default Change Comments
Press
and
at the same time to get to P 00 or P 15
P 15 Set time 00:00 23:59 00:01 00:00
hour:minute
P 16 Set date 01.01 12.31 00.01 01.01
month.day
P 17 Set year 0 9999 1 1995
P 18 Curve point x1 –9 °C 19 °C 1 °C 5 °C See curve below
P 19 Curve point y0 P 20 120 °C 1 °C 60 °C See curve below
P 20 Curve point y1 P 21 P 19 1 °C 45 °C See curve below
P 21 Curve point y2 5 °C P 20 1 °C 18 °C See curve below
P 22 Min. supply temp. 0 °C P 23 0,5 °C 10 °C See curve below
P 23 Max. supply temp. P 22 120 °C 0,5 °C 80 °C See curve below
Dämpad
10
20
30
40
50
60
80
-10 0 5-5 10 15 20-15 25-20-25
P 19
P 21
P 20
P 18
70
-30
P 23
P 22
P 05
Parallel
shift ±°C
y0
y1
y2
x0 x1 x2
Damped
P 24 P band, supply controller 10°C 200°C 0,5°C 100°C
P 25 Run time for actuator 0 s 300 s 5 s 300 s
P 26 Max. incr. rate supp. setpt. 1 °C/m 50 °C/m
0,
1°C/m 2 °C/m Ramp limitation
P 27 Automatic curve adjustmt. 0 (off) 1 (on) 1 1 (on) With ref. sensor only
P 28 I time for curve adj. reg. 1 m. 720 m. 1 m. 180 m. With ref. sensor only
P 29 Max. curve adjustment 0 °C 40 °C 1 °C 5 °C With ref. sensor only
P 30 Room control effect, day 0,5 20 0,5 2 With ref. sensor only
P 31 Room control effect, night 0,5 50 0,5 10 With ref. sensor only
P 32 Dead zone, room 0 °C 5 °C 0,1 °C 0,3 °C With ref. sensor only
P 33 Outd. temp., 0% night setb. -30 °C P 34 1 °C –10 °C Affects morning boost
P 34 Out. tmp., 100% night setb. P 33 20 °C 1 °C 10 °C Affects morning boost
P 35 Adaptive start time optim. 0 (off) 1 (on) 1 1 (on) With ref. sensor only
P 36 Max. morning boost 0 °C 100 °C 1 °C 10 °C See curve
0%
100%
-10 0 5-5 10 15 20-15 25-20-25
P 34
P 33
Damped
10
-10 0 5-5 10 15 20-15 25-20-25
P 36
0
(°C)
Morning boost
P 34
P 33
Damped