TAC 2112, Manual Commissioning Protocol / List of Parameters
TAC AB, 1999-08-01 0-004-7459-3 (GB), A:5(6)
P No. Parameter Min. Max. Step Default Change Comments
P 74 Supply temp. pump stop 0°C 120°C 1°C 20°C
P 75 Exercise on/off 0 (off) 1 (on) 1 1 (on) 0=off, 1=on
P 76 Min. off time for pump 0 h 12 h 0,5 h 2 h h=hours
P 77 Adjustment, outdoor sensor -5 °C 5 °C 0,25 °C 0°C
P 78 Adjustment, ref. sensor –5 °C 5 °C 0,25 °C 0 °C With ref. sensor only
P 79 Damping const., outd. temp 0 h 20 h 1 h 4 h 0=no damping, h=hours
P 80 Current SPC effect (-1)•P81 P 81 0,1 °C
P 81 SPC effect at +10 V 0 °C 40 °C 1 °C 0 °C
-40
0
5786910432
+40
E
ect on
setpoint (°C)
SPC signal
(V)
P 81
P 82 Alarm, pump 0 1 1
0=no alarm, 1=alarm
P 83 Alarm, supply temp. 0 1 1
0=no alarm, 1=alarm
P 84
P 85
P 86
P 87
P 88
P 89 Man. cont., outd. sensor sig.
(Y2)
0 V 10 V 0,1 V
P 90 Man. cont. of pump (K1) 0 1 1
0=off, 1=on
P 91 Man. cont., output (K2) 0 1 1
0=off, 1=on
P 92 Man. cont., buzzer alarm
(K3)
0 1 1
0=off, 1=on
P 93 Man. cont., weekly program
2 (K4)
0 1 1
0=off, 1=on
P 94 Man. cont., heating (K5/K6) 0 1 1
–1=close, 1=open, 0=off
P 95 Serial number (part 1) 0000 9999 1 *
* as per type label
P 96 Serial number (part 2) 0000 9999 1 *
* as per type label
P 97
P 98
P 99 Display test, etc. - - -