For 220V 30HP and above and 440V 40HP,the maximum output frequency is 
100Hz 
. ND mode is only applied to V / f and V / f + PG mode. SLV, SV, PMSV and PMSLV 
modes do not provide a normal load mode.   
00- 28  Command characteristic selection of master frequency 
Range 
【0】:
 Positive characteristic (0~10V/4~20mA corresponds to 0~100%) 
【1】: Negative characteristic (0~10V/4~20mA corresponds to 100~0%) 
 
‧When inputting analog frequency reference signal from the control terminal AI1 or       
AI2, select the characteristic of main frequency reference command corresponding 
to the analog signal.   
‧00-28 = 0: Positive characteristic of main frequency reference command. 
            (0-10V or 4-20mA /0-100%, -10-0V/-100%-0) 
          =1: Negative characteristic of main frequency reference command. 
‧Please refer to Figure 4.3.10 for the characteristics of the main frequency     
reference  
 
 
‧ Figure 4.3.10 Positive/Negative characteristic of main frequency reference command. 
 
 
00- 29  Zero-speed operation selection 
Range 
【0】:
 Operation based on frequency command 
【1】: Stop 
【2】: Operation based on lowest frequency 
【3】:
 Zero-speed operation 
 
In sensor vector mode (SV / PMSV) (00 - 00 = 3 / 4), when the operation frequency is 
below the minimum output frequency, as shown in Figure 4.3.11.