3-3
3.2 Installation
3.2.1 Installation space
(1) Please install the A510 inverter in vertical direction, leaving enough space to
ensure the cooling effect, shown in Figure 3.1.
Avoid the upside-down or horizontal installation.
Figure 3.1 A510 Installation Space
(2) The temperature of inverter’s radiator cooling fins may reach 90 in operation.
Therefore, the contact surface for the inverter installation shall be made by the high-
temperature-resistant material.
When the inverter is operating in the power distribution box, the environment must be
ventilated and the environmental temperature must be less than +40 ° C.
Up side
Down side
Right
Left
X= for the inverter capacity of 18.5kW (including the
smaller capacity), the minimum width is recommended
as 100mm.
X= for the inverter capacity of 22 kW (including the
higher capacity), the minimum width is recommended
as 200mm.