4-212 
4.4.3  Application command  
 
1. Counter 
 
 
c 
Counting mode (1-4) 
d 
UP/Down counting modes can be set by    (I1 ~ f8). 
  OFF:Up counting (0,1,2,3…) 
  ON: Down counting(…3,2,1,0) 
e 
Use (I1~f8) to reset counting value     
  ON : Count value resets and h is OFF 
  OFF : Count value keeps on counting 
f 
Present counting value of the counter   
g 
Counter setting action values (AS1~AS4,MD1~MD4,T1~T8,C1~C8,V1~V7,constant) 
h 
Counter number (from C1 to C8, there are 8 groups in total) 
The description of counting mode: 
mode 1: 
Count value is locked to the set value. The value will not be retained when the power is 
cut off. 
mode 2: 
Count value is not locked. The value will not be retained when the power is cut off. 
mode 3: 
Count value is locked. The value will be retained when the power is cut off. 
mode 4: 
Count value is not locked. The value will be retained when the power is cut off. 
 
(1) Counter mode 1 
 
Example : 
 
In