5-5 
5.3 Warning / self-diagnosis detection function 
When the inverter detects a warning, the digital operator will display the warning code (flash), and the 
fault output contact will not act. Once the warning is removed, the system will automatically restore the 
original state.   
When the inverter detects a self-diagnosis function (for example, there is an invalid setting or two 
parameters are contradictive), the digital operator will display the self-diagnosis code, and the fault output 
contact will not act. Before the parameter has been correctly set, the inverter can not execute the operation 
command.  
When a warning or a self-diagnostic error occurs, refer to Table 5.2 to confirm and correct the error. 
When the RESET key is pressed at this time, the warning message (flash) disappears. If the warning or 
self-diagnostic error still exists, the warnings will be displayed again in 5 seconds. 
 
  
Table 5.2 warning / self-diagnosis and corrective actions 
LED  display    Description   Possible causes    Corrective action   
OV 
( flash ) 
 over voltage   
 
Voltage of main circuit:   
The DC bus voltage exceeds 
the OV detection level, and 
the inverter has stopped. 
410Vdc: 230 V class 
820Vdc: 460 V class 
The input power voltage is too 
high. 
  Check the input power 
voltage 
UV 
( flash ) 
 under voltage  
 
Voltage of main circuit:   
The DC bus voltage is lower 
the UV detection level, and 
the inverter has stopped. 
190Vdc: 230V class 
380Vdc: 460V class 
(07-13 can set the detection 
level) 
. The input power voltage is   
too low. 
. Momentary power loss   
occurs. 
 
. Check the input power   
voltage.  
.Check the input circuit. 
.Check the main circuit MC. 
OH2 
( flash ) 
Inverter over 
heating 
warning 
 
Inverter over heating warning: 
Use multi function digital input 
terminals to input the inverter 
over heating warning. 
(03-00 ~03-07=31) 
Multi function digital input 
terminal receives the 
occurrence signal of external 
over heating warning. 
Check the external condition 
OT 
( flash ) 
 over torque 
detection  
 
  over torque detection : 
The inverter output current is 
higher than 08-15 (OT 
detection level )    and 
exceeds set time of 08-16. 
Subject to 08-14=1, the 
inverter continues operation. 
Mechanical load is too big. 
.Check the application or the 
machine’s operation   
status.  
.Check the set values of 
08-15 and 08-16. 
UT 
( flash ) 
 under torque 
detection  
 
  Under torque detection : 
The inverter output current is 
lower than 08-19 (under 
torque detection level ) and 
exceeds set time of 08-20. 
Subject to 08-18=1,the 
inverter continues operation. 
Mechanical load is removed 
momentarily.(for example, 
the belt is broken off) 
.Check the application or the 
machine’s operation status. 
.Check the settings of 08-19 
and 08-20. 
bb1 
( flash ) 
 External block  
 
 External block  ( Terminal  
S1) 
bb2 
( flash ) 
 External block  
 
 External block  ( Terminal  
S2) 
bb3 
( flash ) 
External block  ( Terminal  
S3) 
 
External block input is 
received by multifunction 
digital input terminals. 
 
.Remove the causes of   
external block.