4-70
01- 02 Maximum output frequency of motor 1
Range
40.0~400.0Hz
40.0~1200.0Hz (when 00-31 = 1 )
01- 03
Maximum output voltage of motor 1
Range
220V:0.1~255.0V
400V:0.2~510.0V
01- 04
Middle output frequency 2 of motor 1
Range
0.0~400.0Hz
0.0~1200.0Hz (when 00-31 = 1 )
01- 05
Middle output voltage 2 of motor 1
Range
220V:0.0~255.0V
400V:0.0~510.0V
01- 06
Middle output frequency 1 of motor 1
Range
0.0~400.0Hz
0.0~1200.0Hz (when 00-31 = 1 )
01- 07
Middle output voltage 1 of motor 1
Range
220V:0.0~255.0V
400V:0.0~510.0V
01- 08
Minimum output frequency of motor 1
Range
0.0~400.0Hz
0.0~1200.0Hz (when 00-31 = 1 )
01- 09
Minimum output voltage of the motor 1
Set Range
220V:0.0~255.0V
400V:0.0~510.0V
01- 12 Base frequency of motor 1
Set Range
1
0.0~400.0Hz
1
0.0~1200.0Hz (when 00-31 = 1 )
01- 13 Base output voltage of motor 1
Set Range
220V:0.0~255.0V
400V:0.0~510.0V
V/f curve setting (01-02~01-09 and 01-12~01-13)
Only when 01-00 has been set to "F" or "FF", users can set 01-02 ~ 01-13 ~ 01-09
and 01-12. If 01-00 is set to any other value but not F or FF, the parameter can
not be changed. Please follow the rules of the frequency setting, or the warning
message "SE03" of V / f curve tuning error will be displayed.
F
max
> F
base
> F
mid2
F
mid1
>F
min
(01-02) (01-12) (01-04) (01-06) (01-08)
If 01-04 and 01-05 (or 01-18 and 01-09) are set to 0the program will ignore the set
values of Fmin2 and Vmin2 .
There are not relevant rules for voltage setting (from 01-02 to 01-09).
If the control mode is changed through 00-00 parameters 01-08(F
min
) and 01-09
(V
min
) will change the default settings of various control mode.
Refer to the following V / F curve defined by users.