Figure 4.3.14 Tune torque compensation gain to increase output torque
01-14
Input voltage setting
Range
220V:【155.0~255.0】V
400V:【310.0~510.0】V
Set the inverter voltage by the unit of 0.1V to match the input power (such as. 200V /
208V / 230V / 240V or 380V / 415V / 440V / 460V / 480V).
This setting is used as a reference for pre-defining V / f curve (01-00 = 0 to E) and
protection for over-voltage, stall prevention and so on.
01-15
Torque compensation time
Range
【1~10000】ms
Torque compensation time(01-15)
. Set the torque compensation delay time by the unit of millisecond.
. In general, there is no need to do adjustments, except the following situations:
─In case of motor vibration, increase the setting.
─ If the motor response is too slow, reduce the setting.
01- 16 Maximum output frequency of motor 2
Range
【
40.0~400.0】Hz
【4
0.0~1200.0】Hz (when 00-31 = 1 )
01- 17
Maximum output voltage of motor 2
Range
220V:【0.1~255.0】V
400V:【0.2~510.0】V
01- 18
Middle output frequency 2 of motor 2
Range
【
0.0~400.0】Hz
【
0.0~1200.0】Hz (when 00-31 = 1 )
01- 19
Middle output voltage 2 of motor 2
Range
220V:【0.0~255.0】V
400V:【0.0~510.0】V
01- 20
Middle output frequency 1 of motor 2
Range
【
0.0~400.0】Hz
【
0.0~1200.0】Hz (when 00-31 = 1 )
01- 21
Middle output voltage 1 of motor 2
Range
220V:【0.0~255.0】V
400V:【0.0~510.0】V
01- 22
Minimum output frequency of motor 2
Range
【
0.0~400.0】Hz
【
0.0~1200.0】Hz (when 00-31 = 1 )
01-23
Minimum output voltage of motor 2
Set Range
220V:【0.0~255.0】V
400V:【0.0~510.0】V
01- 24 Base frequency of motor 2