03- 08
(S1~S8)DI scan time
Range
【0】
scan time 4ms
【1】 scan time 8ms
z
When the CPU chip of the inverter scans terminal TM2, if there are the same
signals input by N consecutive times (namely, the number of scan), then the
inverter will consider it as normal execution signal; if the number is less than N,
then the inverter will consider it as noise.
z
A scan time is 4ms.
z Users can determine the interval time of scan based on the impact degree from
the noise of environment. When the noise is severe, tune 03—08 to 1, but this
tuning will lead to slower response speed.
03- 09 Multi-function terminal S1-S4 type selection
Range
【
xxx0b】: S1 A contact 【xxx1b】: S1 B contact
【
xx0xb】: S2 A contact 【xx1xb】: S2 B contact
【
x0xxb】: S3 A contact 【x1xxb】: S3 B contact
【
0xxxb】: S4 A contact 【1xxxb】: S4 B contact
03- 10 Multi-function terminal S5-S8 type selection
Range
【
xxx0b】: S5 A contact 【xxx1b】: S5 B contact
【
xx0xb】: S6 A contact 【xx1xb】: S6 B contact
【
x0xxb】: S7 A contact 【x1xxb】: S7 B contact
【
0xxxb】: S8 A contact 【1xxxb】: S8 B contact
¾ When general terminals are used, they shall be connected to switch. The switch has
different type, for example, the normally open switch and the normally close switch.
You have to pay attention to this when selecting the switch for application, because
the work status of these two types of switch is different. This parameter determines
the requirement of the normally open switch or the normally close switch.
Each bit of 03-09/03-10 presents as below:
03-09= 0
0 0 0 0: normally open switch
s4 s3 s2 s1
1: normally close switch
03-10= 0
0 0 0 0: normally open switch
s8 s7 s6 s5
1: normally close switch
The switch input type is selected by users.
Example : if you want S1 and S2 to be connected to the normally close switch, then you
can set 03- 09=0011.
Note: Before setting terminals to connect the normally open/normally close switch, do
not set the operation command to the control from external terminals, otherwise it
will cause unnecessary harm.