4-103
04-- External terminal analog signal input(output) function group
04- 00
AI input signal type
Range
【0】:
AI1 0~10V AI2 0~10V
【1】: AI1 0~10V AI2 4~20mA
【2】: AI1 -10~0~10V AI2 0~10V
【3】: AI1 -10~0~10V AI2 4~20mA
04- 01
AI1 signal scanning and filtering time
Range
【
0.00~2.00】Sec
04- 02
AI1 gain value
Range
【
0.0~1000.0】%
04- 03
AI1bias voltage value
Range
【
-100~100.0】%
04- 05
AI2 function setting
Range
【0】:
Auxiliary frequency
【1】:
Frequency Reference Gain
【2】:
Frequency Reference bias
【3】:
Output Voltage Bias
【4】:
Coefficient of acceleration and deceleration reduction
【5】:
DC braking current
【6】:
Over-torque Detection Level
【7】: Stall prevention Level During Running
【8】:
Frequency lower limit
【9】:
Jump frequency 4
【10】:
Added to AI1
【11】:
Positive torque limit
【12】:
Negative torque limit
【13】:
Regenerative Torque Limit
【14】:
Positive / negative torque limit
【15】:
Torque command/ Torque limit (in speed control)
【16】:
Torque compensation
【17】:
No function
04- 06
AI2 signal scanning and filtering time
Range
【0.00~2.00】Sec
04- 07
AI2 gain value
Range
【
0.0~1000.0】%
04- 08
AI2 bias voltage value
Range
【
-100.0~100.0】%
(1) Analog Input Level Adjustment AI1, AI2 (04-02, 04-03, 04-07, 04-08)
. For each of the different analog inputs AI1and AI2, the corresponding gain and bias should be listed
separately.
AI1 is adjusted by 04-02 and 04-03, AI2 is adjusted by 04-07 and 04-08. As to the analog input and
related parameter, please refer to Figure 4.3.35.