4-103
04-- External terminal analog signal input(output) function group
04- 00
AI input signal type
Range
0:
AI1 0~10V AI2 0~10V
1: AI1 0~10V AI2 4~20mA
2: AI1 -10~0~10V AI2 0~10V
3: AI1 -10~0~10V AI2 4~20mA
04- 01
AI1 signal scanning and filtering time
Range
0.00~2.00Sec
04- 02
AI1 gain value
Range
0.0~1000.0%
04- 03
AI1bias voltage value
Range
-100~100.0%
04- 05
AI2 function setting
Range
0:
Auxiliary frequency
1:
Frequency Reference Gain
2:
Frequency Reference bias
3:
Output Voltage Bias
4:
Coefficient of acceleration and deceleration reduction
5:
DC braking current
6:
Over-torque Detection Level
7: Stall prevention Level During Running
8:
Frequency lower limit
9:
Jump frequency 4
10:
Added to AI1
11:
Positive torque limit
12:
Negative torque limit
13:
Regenerative Torque Limit
14:
Positive / negative torque limit
15:
Torque command/ Torque limit (in speed control)
16:
Torque compensation
17:
No function
04- 06
AI2 signal scanning and filtering time
Range
0.00~2.00Sec
04- 07
AI2 gain value
Range
0.0~1000.0%
04- 08
AI2 bias voltage value
Range
-100.0~100.0%
(1) Analog Input Level Adjustment AI1, AI2 (04-02, 04-03, 04-07, 04-08)
. For each of the different analog inputs AI1and AI2, the corresponding gain and bias should be listed
separately.
AI1 is adjusted by 04-02 and 04-03, AI2 is adjusted by 04-07 and 04-08. As to the analog input and
related parameter, please refer to Figure 4.3.35.