Examples for wiring the periphery devices of A510 are shown in the following:
電源
無熔絲開 NFB
(及漏電斷路器)
電磁接觸
AC 電抗
輸入側雜
濾波器
變頻器
零相雜訊濾波器
三相感應
馬達
外加高速保險絲
No fuse breaker (NFB) and Leakage Circuit
Breaker
Please refer to table 3 for choosing NFB of
appropriate current.
Do not use NFB to control the start/stop of the
inverter.
If a leakage circuit breaker is added for leakage
protection, its current sensitivity shall be more
than 200mA and action time more than 0.1 (V-
TYPE), so as to avoid high-frequency
malfunction.
Electromagnetic contactor
It can not add the electromagnetic contactor for
general use. However, for the application
requiring external sequence control or
automatic restart function after power cut, an
electromagnetic contactor is required.
Please avoid using electromagnetic contactor
for the start/stop control of the inverter as
possible.
AC reactor
In case of further improving the power factor or
suppress the external surge, an AC reactor can
be additionally equipped.
Fast acting fuse
To protect interface devices, it is necessary to
add a fast acting fuse (fuse specification will be
referred to Section 6.6)
Input Noise filter
A510 is matched with TECO special filter,
meeting the EN 55011 class A criterion.
The selection of input noise filter can be
referred to Section 6.4)
Inverter
Terminal R,S,T at input side have no phase
sequence requirement, thus they can be
arbitrarily exchanged.
Terminal E must be well grounded.
Power supply
No Fuse Breaker
(NFB) and Leakage
Circuit Breaker
Electromagnetic
contactor
AC reactor
Fast acting fuse
Input Noise filter
Inverter
Zero-phase
noise filter
3-phase
induction
motor