5-9
LED display Description Possible causes Corrective action
exceeds the allowed range.
.
parameter setting will be
based on the other
parameter setting( for
example 02-00>02-01,
02-20>02-21 or
00-12>00-13 and so on).
SE02
Digital input
terminal error
Errors of multifunction digital
input terminal
Errors of multifunction digital
input terminals (03-00 to
03-07), as described in the
following:
1UP/DOWN commands are
not set at the same time( they
must be used together).
2 UP/DOWN commands (08
and 09) and ACC/DEC
commands (11) are set at the
same time.
3 Speed search 1 (19,
maximum frequency) and
Speed search 2 (34, from
the set frequency) are set at
the same time.
Check the parameter setting
SE03
V/f curve error
V/f curve setting error:
V/F curve setting is not based
on the following architecture:
1 01-02 > 01-12 >01-06 >
(Fmax) (Fbase) (Fmid1)
01-08;
(Fmin)
201-16 > 01-24 >
01-20 > 01-22;
(Fmax(2)) (Fbase(2))
(Fmid(1)) (Fmin(2))
Confirm V/F parameter
setting.
SE05
PID selection
error
PID selection error:
10-00 and 10-01are all set to
1(AI1) or 2 (AI2) at the same
time.
Check the set values of
paramters10-00, 10-01
HPErr
Model selection
error
Inverter capacity setting error:
Inverter capacity setting 13-00
does not match the rated
voltage.
The inverter capacity setting
13-00 does not match the
voltage class of the hardware.
Check the inverter capacity
setting 13-00matches the
voltage class of the
hardware or not.
SE07
PG card error
Inverter PG card setting error
This inverter PG card has not
been installed.
Check the inverter PG
device.
Check the control mode
SE08
PM Motor mode
error
A510 inverter of this horse
power does not support the
PM Motor mode
Inverter does not support PM
Motor mode
Check the control mode
SE09
PI setting error
Inverter PI setting error
Inverter PI option (03-30)
selection conflicts with
PID source (10-00 and
10-01).
Check inverter PI option
(03-30) selection and PID
source (10-00 and 10-01)

Table of Contents

Related product manuals