2. When MODBUS communication protocol is used to communicate with outside, no
more than 31 inverters can be connected in parallel. If multiple inverters are
connected, a resistor of 220Ω must be connected to both sides of the RS-485 COM
port of the last inverter.
3. Please refer to "A510 RS-485 MODBUS communication function application
manual."
b. Wiring example of PROFIBUS communication protocol
‧ A PROFIBUS model (JN5-CM-PDP) requires to be added for the
communication of PROFIBUS-DP.
220
Ω
電阻
7200 MA
M1
P
1
2
3
4
5
TB1
S(+)
S(-)
1
2
3
TB2
P
MA-SP
7200 MA
M2
P
1
2
3
4
5
TB1
S(+)
S(-)
1
2
3
TB2
P
MA-SP
7200 MA
P
1
2
3
4
5
TB1
S(+)
S(-)
1
2
3
TB2
P
MA-SP
M31
220
Ω
電阻
DC24V
PROFIBUS-DP
控制器
Figure 53 Wiring example of PROFIBUS communication protocol
Note: 1. For the power consumption of each PROFIBUS / Devicenet module,
the power supply with appropriate capacity should be selected according to the
TP03
TP03
TP03
Resistor