4-75
12-Monitoring Parameters
12-00
Display Mode
Range
Highest digit => 0 0 0 0 0 <= lowest digit
00000~77777 Each digit can be set from 0 to 7 as listed below.
0: Disable display
1: Output Current
2: Output Voltage
3: DC voltage
4: Temperature
5: PID feedback
6: AVI
7: ACI
MSD= Most significant digit. LSD= Least significant digit.
The highest bit is used for power-up monitor. The 4 least significant bits can be used to customize the display
sequence.
12-01
PID Feedback Display Mode
Range
0: Displayed as Integer (xxx)
1: Display the feedback value with one place after the decimal point (xx.x)
2: Display the feedback value (x.xx) with two places after the decimal point
12-02
PID Feedback Display Unit Setting
Range
0:xxx--
1:xxxpb(pressure)
2:xxxfl(flow)
12-03
Custom Units (Line Speed) Display Mode
Range
0~65535rpm
Set motor rated RPM in this parameter to display motor RPM instead of output frequency.
The line speed display is linearly proportional to the output frequency 0 to 50Hz or 0 - 60 Hz as appropriate.
Motor synchronous speed = 120 x motor rated frequency ÷ Number of poles.
12-04
Custom Units (Line Speed) Display Mode
Range
0:Drive Output Frequency is displayed
1:Line Speed is Displayed in Integer (xxxxx)
2:Line Speed is Displayed with one place after the decimal point (xxxx.x)
3:Line Speed is Displayed with two places after the decimal point (xxx.xx)
4:Line Speed is Displayed with three places after the decimal point (xx.xxx)
12-04≠0, line speed is displayed when the inverter is running or stopped.