4-75
Highest digit => 0 0 0 0 0 <= lowest digit
00000~77777 Each digit can be set from 0 to 7 as listed below.
【0】: Disable display
【1】: Output Current
【2】: Output Voltage
【3】: DC voltage
【4】: Temperature
【5】: PID feedback
【6】: AVI
【7】: ACI
MSD= Most significant digit. LSD= Least significant digit.
The highest bit is used for power-up monitor. The 4 least significant bits can be used to customize the display
sequence.
PID Feedback Display Mode
【0】: Displayed as Integer (xxx)
【1】: Display the feedback value with one place after the decimal point (xx.x)
【2】: Display the feedback value (x.xx) with two places after the decimal point
PID Feedback Display Unit Setting
【0】:xxx--
【1】:xxxpb(pressure)
【2】:xxxfl(flow)
Custom Units (Line Speed) Display Mode
Set motor rated RPM in this parameter to display motor RPM instead of output frequency.
The line speed display is linearly proportional to the output frequency 0 to 50Hz or 0 - 60 Hz as appropriate.
Motor synchronous speed = 120 x motor rated frequency ÷ Number of poles.
Custom Units (Line Speed) Display Mode
【0】:Drive Output Frequency is displayed
【1】:Line Speed is Displayed in Integer (xxxxx)
【2】:Line Speed is Displayed with one place after the decimal point (xxxx.x)
【3】:Line Speed is Displayed with two places after the decimal point (xxx.xx)
【4】:Line Speed is Displayed with three places after the decimal point (xx.xxx)
12-04≠0, line speed is displayed when the inverter is running or stopped.