4-17
Group 09: Communication Parameters
Code
Parameter Name
Setting Range
Default
Unit
Notes
09-00
Assigned Communication Station
Number
1~32
1
-
*2*3
09-01
Communication Mode Select
0: RTU Code
0
-
*2*3
1: ASCII Code
2: BACnet
09-02
Baud Rate Setting (bps)
0: 4600
2
bps
*2*3
1: 9600
2: 19200
3: 38400
09-03
Stop Bit Selection
0: 1 Stop Bit
0
-
*2*3
1: 2 Stop Bits
09-04
Parity Selection
0: No Parity
0
-
*2*3
1: Even Parity
2: Odd Parity
09-05
Data Format Selection
0: 8-Bits Data
0
-
*2*3
1: 7-Bits Data
09-06
Communication time-out detection
time
0.0 ~ 25.5
0.0
s
09-07
Communication time-out operation
0: Deceleration to Stop (00-15)
0
-
1: Coast to Stop
2: Deceleration to Stop (00-17)
3: Continue Operating
09-08
Error 6 verification time
1 ~ 20
3
09-09
Drive Transmit delay Time (ms)
5 ~ 65
5
ms
09-10
BACnet Stations
1 - 124
1
Group 10: PID Parameters
Code
Parameter Name
Setting Range
Default
Unit
Notes
10-00
PID target value selection
(when 00-05\00-06=6
,this function is enabled)
0: Potentiometer on Keypad
1
-
*1
1: Analog Signal Input (AVI)
2: Analog Signal Input (ACI)
3: Freq. set by Communication
4: Keypad Freq. Parameter 10-02
10-01
PID feedback value selection
0: Potentiometer on Keypad
2
-
*1
1: Analog Signal Input (AVI)
2: Analog Signal Input (ACI)
3: Freq. set by Communication
10-02
0.0 ~ 100.0
50.0
%
*1
10-03
PID Mode Selection
0: Disabled
0
-
1: Deviation D Control. FWD Characteristic
2: Feedback D Control. FWD Characteristic