4-16
Group 08: Protection Parameters
Trip Prevention Level
During Acceleration (%)
Trip Prevention Level
During Deceleration (%)
Trip Prevention Level In
Run Mode (%)
over voltage Prevention
Level in Run Mode
Electronic Motor
Overload Protection
Operation Mode
xxxx0: Disable Electronic Motor Overload
Protection
xxxx1: Enable Electronic Motor Overload
Protection
xxx0x: Motor Overload Cold Start
xxx1x: Motor Overload Hot Start
xx1xx: Invertor Duty Motor ( Force Vent)
Operation After
Overload Protection is
Activated
0: Coast-to-Stop After Overload
Protection is Activated
1: Drive Will Not Trip when Overload
Protection is Activated (OL1)
Over heat Protection
(cooling fan control)
0: Auto (Depends on temp.)
1: Operate while in RUN mode
2: Always Run
3: Disabled
AVR Function
(Auto Voltage
Regulation)
2: AVR function disable for stop
3: AVR function disable for deceleration
4: AVR function disable for stop and
deceleration.
5: When VDC>(360V/740V), AVR function
disable for stop and deceleration.
Input phase lost
protection
3: Continue running, when warning level is
reached. Coast to stop, when protection
level is reached.
PTC Signal Smoothing Time
PTC Detection Level Reset
Fan Control Temperature Level