4-32
03-External digital inputs & Relay Output Parameters
Multifunction Input Term. S1
Multifunction Input Term. S2
Multifunction Input Term. S3
Multifunction Input Term. S4
Multifunction Input Term. S5
【0】:Forward/Stop Command (Parameters 00-02/03=1 & 00-04)
【1】:Reverse/Stop Command (Parameters 00-02/03=1 & 00-04)
【2】:Preset Speed 1 (5- 02) (Parameter Group5)
【3】:Preset Speed 2 (5- 03) (Parameter Group5)
【4】:Preset Speed 4 (5- 05) (Parameter Group5)
【6】:JOG Forward Command (Parameters 00-18~00-20)
【7】:JOG Reverse Command (Parameters 00-18~00-20)
【8】:Up Command (Parameters 00-05/06=4 & 03-06/07)
【9】:Down Command (Parameters 00-05/06=4 & 03-06/07)
【10】: 2
nd
Acc/Dec times
【11】: Disable Acc/Dec
【12】: Main/ Alternative run source Select (Parameters 00-02/00-03)
【13】: Main/Alternative Frequency Command Select (Parameters 00-05/00-06)
【14】: Rapid Stop (controlled deceleration stop)
【15】: Base Block (Coast to stop)
【16】: Disable PID Function (Parameter Goup10)
【17】: Reset
【18】: Enable Auto Run Mode (Parameter Group 6)
See examples and function explanation in the following pages.
1): For setting parameters 03-00~03-04 set to【0, 1】External Run/Stop Control, refer to parameter 00-04.
2-wire control method. Mode 1.
Example: FWD/STOP and REV/STOP from two inputs (S1&S2)
Set 00-04 =【0】, S1: 03-00=【0】(FWD/STOP) , S2: 03-01=【1】(REV/STOP)
S1
S2
COM
Forward,
Run / Stop
Reverse
Run / Stop