4-33
S1 ON OFF
FWD
REV
ONOFF
S2
Hz
T
Note: If both forward and reverse commands are active the inverter will treat this as a STOP condition.
2-wire control method. Mode 2.
Example: RUN/STOP and REV/FWD from two inputs ( S1&S2)
Set 00-04 =【1】; S1: 03-00=【0】(RUN/STOP), S2: 03-01=【1】(REV/FWD)
S1
S2
COM
Forward,
Run / Stop
Reverse
Run / Stop
S1 ON OFF
FWD
REV
S2
T
Hz
ON
OFF
3-wire control method.
Example: Two separate push buttons for RUN & STOP and a two position switch for FWD/REV
Set 00-04 to 2 (3 wire control mode), terminals S1, S2 and S3 are now dedicated for use in 3-wire control and
parameter 03-00, 03-01 and 03-02 do not have any effect on the inverter operation.