4-58
06- Auto Run(Auto Sequencer) function
06- 00 Auto Run( sequencer) mode selection
Range
【0】:Disabled
【1】:Single cycle, continues to run from the unfinished step if restarted.
【2】:Periodic cycle, continues to run from the unfinished step if restarted.
【3】:Single cycle, then holds the speed of final step to run. Continues to run
from the unfinished step if restarted.
【4】:Single cycle, starts a new cycle if restarted.
【5】:Periodic cycle, starts a new cycle if restarted.
【6】:Single cycle, then hold the speed of final step to run, starts a new cycle if
restarted.
Frequency of the step 0 is set by parameter 05-01 keypad Frequency.
06- 01 Auto Run Mode Frequency Command 1
06- 02 Auto Run Mode Frequency Command 2
06- 03 Auto Run Mode Frequency Command 3
06- 04 Auto Run Mode Frequency Command 4
06- 05 Auto Run Mode Frequency Command 5
06- 06 Auto Run Mode Frequency Command 6
06- 07 Auto Run Mode Frequency Command 7
Range
【0.00 ~ 599.00】Hz
06- 16 Auto Run Mode Running Time Setting0
06- 17 Auto Run Mode Running Time Setting1
06- 18 Auto Run Mode Running Time Setting2
06- 19 Auto Run Mode Running Time Setting3
06- 20 Auto Run Mode Running Time Setting4
06- 21 Auto Run Mode Running Time Setting5
06- 22 Auto Run Mode Running Time Setting6
06- 23 Auto Run Mode Running Time Setting7
Range
【0.00 ~ 3600.0】Sec
06- 32 Auto Run Mode Running Direction0
06- 33 Auto Run Mode Running Direction1
06- 34 Auto Run Mode Running Direction2
06- 35 Auto Run Mode Running Direction3
06- 36 Auto Run Mode Running Direction4
06- 37 Auto Run Mode Running Direction5
06- 38 Auto Run Mode Running Direction6
06- 39 Auto Run Mode Running Direction7
Range
【0】: STOP
【1】: Forward
【2】: Reverse
Auto Run sequencer mode has to be enabled by using one of the multifunctional inputs S1 to S5
and setting the relevant parameter 03-00 to 03-04 to selection【18】.
Various Auto Run (sequencer) modes can be selected by parameter (06-00) as listed above.
7 Auto Run (sequencer) modes can be selected by parameters (06-01~06-39)
Auto Run frequency commands1 to 7 are set with Parameters (06-01 ~ 06-07),
Sequence run times are set with parameters (06-17 ~ 06-23)