5-5 
5.1.3 Special conditions 
Display  Fault  Description 
StP0 
Zero speed at stop 
In V/f mode, STP0 comes out at less than 1.3Hz (50Hz set) or at 
less than 1.5Hz (60Hz set) 
In SLV mode, STP0 comes out at less than 1Hz 
 
StP1 
Fail to start directly 
On power up. 
1. If the inverter is set for external terminal control mode 
(00-02/00-03=1) and direct start is disabled (07-04=1) 
2. The inverter cannot be started and will flash STP1. 
3. The run input is active at power-up, refer to descriptions 
of (07-04). 
 
StP2 
Keypad Stop 
Operated when   
inverter in external 
Control mode. 
1.  If the Stop key is pressed while the inverter is set to 
external control mode (00-02/00-03=1) then‘STP2’flashes   
after stop.   
2.  Release and re-activate the run contact to restart the 
inverter. 
 
E.S. 
External 
Rapid stop 
When external rapid stop input is activated the inverter will 
decelerate to stop and the display will flash with E.S. message. 
 
b.b. 
External base block 
When external base block input is activated the inverter stops 
immediately and then the display will flash with b.b. message. 
 
PdEr 
PID feedback loss  PID feedback loss is detected. 
 
Alter 
auto tuning error  other errors show up in the process of auto tuning. 
 
OH3 
motor over heat 
warning 
If 08-10 = 3,When over temperature is detected by signal at 
terminal AVI increasing above the warning detection limit set in 
parameter 08-15, then the display will show “OH3”(motor 
over heat warning level) and the motor will continue to run. 
 
LOPB 
Low pressure error 
  The feedback signal is not connected. 
  Due to feedback value of pump pressure is lower than limit of 
minimum flow. 
 
HIPB 
High pressure error 
Due to feedback value of pump pressure is lower than limit of 
maximum flow. 
 
COPUP 
Breaking error of 
multiple pumps 
communication 
Communication breaking or disconnection of pump cascade 
control.