4-29 
  4.3 Parameter Function Description 
00- Basic parameter group 
 
00- 00  Control mode 
Range 
【0】: 
V/F mode   
【1】: 
SLV mode 
Select the relevant control mode for the application, using parameter 00-00 Control mode. 
Default control mode is V/F.   
  V/F mode can be used for most applications specifically multi-motor or applications where auto 
tune is not successful or when a customized V/F pattern may be required.   
Several V/f patterns are available selectable by parameter 01-00. 
Select the appropriate V/f pattern based on the application load type and the motor base 
frequency of 50 or 60 Hz. 
For selections of the V/f patterns. Refer to description of parameter 01-00 
  SLV ( Sensor less vector) is used for obtaining best performance from a motor. Specially at low 
speeds or for applications with dynamic speed change. 
 
00- 01  Motor Direction Control 
Range 
【0】: Forward         
【1】: Reverse 
  00 - 01 Is valid in key pad mode only. 
※Note: When Reverse function is disabled by parameter 11- 00=1 setting 00-01 to 1 .” LOC” will be 
displayed 
 
00- 02  Main Run Command Source selection 
00- 03  Alternative Run Command Source selection   
Range 
【0】: Keypad 
【1】: External Run/Stop Control 
【2】: Communication 
  Parameter 00 - 02/00- 03 sets the inverter operation command source. For switching between 
00-02 and 00-03, use any of the external inputs S1 to S5 and set the relevant parameters (03-
00~03-04) to [12]. refer to parameter group3.
 
 
00- 04  Operation modes for external terminals 
Range 
【0】: Forward/stop-reverse/stop 
【1】: Run/stop-forward/reverse 
【2】: 3-wire control mode -run/stop 
  Parameter 00-04 sets the function of the External Run/Stop and it is used in conjunction 
with Parameters
. 
 
00-02(Main Run Source) = 1 or 00-03(Alternative Run source) = 1   
(When 00-02/00-03=1, the command comes from External Run /Stop) 
 
Parameters 03-00 to 03-04, which are used to set the required function for the digital inputs [S1 
to S5](multi-function inputs).   
 
Note1: Parameters 03-00 to 03-04 are only Required for External Run/stop   
(Two wire control mode). 
Note2: For External Run /Stop control set parameters in the following order: