3-12
3.3.2 Power Cables. 
 
Supply power cable must be connected to TM1 terminal block, terminals L1(L) and L3(N) for 
single phase 200V supply, L1(L), L2, L3(N) for three phase 200V supply and L1, L2, L3 for 
three phase 400V supply. 
Motor cable must be connected to TM1 terminals. T1, T2, T3.  
 
Warning:- Connection of Supply line cable to terminals T1,T2& T3 will result in serious 
damage to the drive components.  
 
Example power connections:- Inverter with dedicated power line. 
Inverter IM
Power 
MCCB
 
 
Install a Supply RFI filter or Isolation transformer when the power source is shared 
with other high power electrical equipment as shown below. 
 
Inverter IM
Machine
Insulation transformer
Power 
MCCB
 
 
 
3.3.3 Control Cable selection and Wiring. 
 
Control cables should be connected to terminal block TM2. 
Choose power & Control cables according to the following criteria:- 
 
  Use copper wires with correct diameter and temperature rating of 60/75°C. 
  Minimum cable voltage rating for 200V type inverters should be 300VAC. 
  Route all cables away from other high voltage or high current power lines  
to reduce interference effects. 
Use a twisted pair shielded cable and connect the shield (screen) wire to the ground 
terminal at the inverter end only. Cable length should not exceed 50 meters. 
 
 
 
Inverter IM
Machine
RFI
Filter
Power 
MCCB
 
Shielding sheath 
Protective covering 
Connect the shield to inverter 
ground terminal 
Do not connect this end