5-9 
5.3.2 Troubleshooting for OC, OL error displays 
The inverter displays OC, OL errors
The inverter  output is OK 
Is the output current of each 
phase even?
Any fault values displayed?
Is there Voltage at U,V and W 
output terminals?
Is the output frequency of the 
operating unit displayed?
Is FWD LED illuminated?
Is the main circuit I.G.B.T 
working 
Any visual abnormalities?
Is the current detector 
OK?
Any abnormal indications?
Is the inverter operation OK 
after board replacement ?
Replace the current 
controller
Replace control board
Replace control board
Replace faulty circuit 
board
Replace I.G.B.T
Replace control board
Replace control board
The inverter is faulted
(Perform detailed check)
YES
NO
YES
YES
NO 
YES
NO
YES
YES
NO
YES
NO
NO
NO
YES
YES
NO
NO
Apply power
Input operation command
Input frequency command
Connect the motor to run