Chapter 5 Troubleshooting and maintenance 
5.1 Error display and corrective action 
5.1.1 Manual Reset and Auto-Reset 
 
Faults which cannot be recovered manually 
Display  Content  Cause  Corrective action 
 -OV- 
Voltage too high 
when stopped 
Detection circuit malfunction  Consult with the supplier 
 
 -LV- 
Voltage too low 
when stopped 
‧  Power voltage too low 
‧  Pre-charge resistor or fuse 
burnt out. 
‧  Detection circuit malfunction 
‧  Check if the power voltage is 
correct  
‧  failed resistor or fuse 
‧  Consult with the supplier 
 
 -OH- 
The inverter is 
overheated when 
stopped 
‧  Detection circuit malfunction 
‧  Ambient temperature too high 
or bad ventilation 
Improve the ventilation 
conditions, if no result then 
replace the inverter 
 
OH-C 
The inverter is 
overheated during 
running 
‧  IGBT temperature is too high or 
poor ventilation 
‧  Temperature sensor error or 
circuit malfunctions 
‧  Reduce carrier frequency     
‧  Improve the ventilation 
conditions, if no result then 
replace the inverter 
 
CtEr 
Current Sensor 
detection error 
Current sensor error or   
circuit malfunction 
Consult with the supplier 
 
HPErr 
Inverter capacity 
setting error: 
Inverter capacity 
setting 13-00 does 
not match the rated 
voltage. 
The inverter capacity setting 
(13-00) does not match the 
hardware voltage levels 
Check the inverter capacity 
setting (13-00) to meet the 
hardware voltage levels. 
 
Err4 
CPU Unusual 
interruption 
External noise interference   
‧  Remove the interference 
source then restart by 
switching power OFF/ON 
‧  If not resolved then consult 
  with the supplier 
 
EPr 
EEPROM problem  Faulty EEPROM  Consult with the supplier 
 
COt 
Communication 
error 
Communications disruption  Check the wiring