4-100
14-73 Slave Wake-Up Selection
Range
0: Disable
1: Enable
When multiple pumps are in parallel and the requirements of slave wake-up can not be achieved in
tolerance range, user can set parameter 14-73=1 and refer to the following
conditions to wake up Slave.
Master is in full speed operation (01-02 maximum output frequency) but pressure feedback
value can not achieve the target pressure value.
Slave is forced to start after 30secs+the value of 14-30, even if the requirement of sleep to wake-up
is not achieved and the pressure feedback value is under the tolerance range of constant pressure)
and keeps operation to achieve the target pressure value.
It is required to follow the formula (the set method 1) and refer to the following diagram to set
the wake-up requirements.
Diagram of requirements for waking up slave