5-14 
5.4 Routine and periodic inspection 
To ensure stable and safe operations, check and maintain the inverter at regular intervals. 
Use the checklist below to carry out inspection. 
Disconnect power after approximately 5 minutes to make sure no voltage is present on the output terminals 
before any inspection or maintenance.   
 
Items Details 
Checking 
period 
Methods Criteria Remedies 
Daily 1Year
Environment & Ground connection 
Ambient 
conditions at 
the installation 
Confirm the temperature 
and humidity at the machine
◎ 
   
Measure with 
thermometer 
and 
hygrometer  
Temperature: 
 -10 ~40°C 
(14~120°F) 
Humidity: 
Below 
95%RH 
Improve the 
ambient or 
relocate the 
drive to a 
better area. 
Installation 
Grounding 
Is the grounding resistance 
correct? 
   
◎ 
Measure the 
resistance 
with a 
multi-tester 
200Vclass: 
below 100Ω 
Improve the 
grounding if 
needed. 
Terminals & Wiring 
Connection 
terminals 
Any loose parts or 
terminals? 
    ◎ 
Visual check 
Check with a 
screwdriver 
Correct 
installation 
requirement 
Secure 
terminals and 
remove rust 
Any damage to the base ?     
◎ 
Any corroded Terminals?      ◎ 
Wiring 
Any broken wires?      ◎ 
Visual check 
Correct wiring 
requirement 
Rectify as 
necessary 
Any damage to the wire 
insulation? 
    ◎ 
voltage 
Input power 
voltage 
Is the voltage of the main 
circuit correct? 
◎ 
   
Measure the 
voltage with a 
multi-tester 
Voltage must 
conform with 
the spec. 
Improve input 
voltage if 
necessary. 
Circuit boards and components 
Printed circuit 
board 
Any contamination or 
damage to printed circuit 
board?          
    ◎ 
Visual check 
Correct 
component 
condition 
Clean or 
replace the 
circuit board 
Power 
component 
Any dust or debris      ◎ 
Clean 
components 
Check resistance between   
terminals 
    ◎ 
Measure with 
a multi-tester 
No short 
circuit or 
broken circuit 
in three 
phase output 
Consult with 
the supplier 
Cooling System 
Cooling fan 
Unusual vibration and 
noise?  
 
◎ 
Visual and 
sound check 
Correct 
cooling 
Consult with 
the supplier 
Excessive dust or debris    ◎ 
Visual check 
Clean the fan
Heat sink  Excessive dust or debris  ◎ 
Clean up 
debris or dust
Ventilation Path 
Is the ventilation path 
blocked? 
◎ 
Clear the 
path