3.3.5 Failure liability 
 
  Teco bears no responsibility for any failures or damaged caused to the inverter if the 
recommendations in this instruction manual  have not been followed specifically 
points listed below,  
 
  If a correctly rated fuse or circuit breaker has not been installed between the power 
source and the inverter. 
 
  If a magnetic contactor, a phase capacitor, burst absorber and LC or RC circuits have 
been connected between the inverter and the motor. 
 
  If an incorrectly rated three-phase squirrel cage induction motor has been used 
 
Note: 
When one inverter is driving several motors, the total current of all motors running 
simultaneously must be less than the rated current of the inverter, and each motor has 
to be equipped with a correctly rated thermal overload relay.