5-4 
5.1.2 Keypad Operation Error Instruction 
Display  content  Cause  Corrective action 
LOC 
1.Parameter   
already locked       
2.Motor direction   
locked  
3.Parameter  
password (13-07)   
enabled 
1.Attempt to modify   
frequency parameter while   
13-06>0.  
2.Attempt to reverse   
direction when 11- 00=1.   
3.Parameter (13 - 07) enabled,   
set the correct password will   
show LOC. 
1.Adjust 13-06 
2.Adjust 11-00 
 
Err1 
Keypad operation 
error 
1.Press ▲ or ▼while 00-05/00-06 
> 0 or running at preset speed. 
2.Attempt to modify the parameter. 
can not be modified during   
operation (refer to the parameter 
list) 
1.The ▲ or▼ is available for   
modifying the parameter only 
when 00-05/00-06=0 
2.Modify the parameter in   
STOP mode. 
 
Err2 
Parameter setting 
error 
1. 00-13 is within the range of   
(11-08 ±11-11)   
OR (11-09 ±11-11)   
OR (11-10 ±11-11) 
2. 00-12  ≦  00-13 
3. 00-05/00-06 or 10-00/10-01 set 
the same value 
4. Modifying parameters 01-01 to 
01-09 when 01-00≠7.  
5. a.If this parameter is 
parameterized for both 
functions (AVI/PTC) at the 
same time. 
b.PTC function is enabled   
by setting 08-10≠0; 
6. Parameter password (13-07) 
set incorrect 
1.modify 11-08~11-10 or 11-11 
2.00-12>00-13 
3.set 00-05 / 00-06 or 10-00 / 
10-01 to be different value 
4.set 01-00=7 
5.PTC function source can not be 
the same as frequency source or 
PID command via AVI. 
6.Please set correct password 
 
Err5 
Modification of 
parameter is not 
available in 
communication 
1.Control command sent   
during communication. 
2.Attempt to modify the   
function 09-02~ 09-05   
during communication 
1.Issue enable command   
before communication 
2.Set parameters 09-02~   
09-05 function before   
communication 
 
Err6 
Communication failed 
1.Wiring error 
2.Communication  
Parameter setting error. 
3.Incorrect communication   
protocol  
4.Communication ground 
disconnected 
5.External noise 
1. Check hardware and wiring 
2.Check Functions(09-00~ 
09- 05). 
3.CON2 needs to connect to the 
earth. 
4.Please increase the setting value 
of 09-08 
 
Err7 
Parameter conflict 
1.Attempt to modify the   
function 13-00/13-08. 
2. Voltage and current   
detection circuit is abnormal. 
If reset is not possible, please 
consult with the supplier.