5-2
Faults which can be recovered manually and automatically
Display Content Cause Corrective action
OC-A
Over-current at
acceleration
Acceleration time too short
The capacity of the motor
exceeds the capacity of the
inverter
Short circuit between the
motor coil and the case
Short circuit between motor
wiring and ground
IGBT module damaged
Set a longer acceleration time
Replace inverter with one that
has the same rating as that of
the motor
Check the motor
Check the wiring
Consult with the supplier
OC-C
Over-current at
fixed speed
Transient load change
Transient power change
Increase the capacity of the
inverter
Install inductor on the power
supply input side
OC-d
Over-current at
deceleration
The preset deceleration time is
too short.
Set a longer deceleration time
OC-S
Over current at
start
Short circuit between the
motor coil and the case
Short circuit between motor
coil and ground
IGBT module damaged
Inspect the motor
Inspect the wiring
Consult with the supplier
OV-C
Excessive
Voltage during
operation/
deceleration
Deceleration time setting too
short or excessive load inertia
Power voltage varies widely
(fluctuates)
Set a longer deceleration time
Consider use of a brake resistor
and/or brake module (For 400V
models or 200V 5hp~15hp
models)
Consider use of a reactor at the
power input side
PF
Input phase Loss
Abnormal fluctuations in the
main circuit voltage
Check the main circuit power
supply wiring.
Check the power supply voltage
LPBFT
Low pressure
fault
Since feedback value of pump
pressure is lower than limit of
minimum flow.
Check feedback signal is
correct and with connection.
Check if feedback value of
pressure is lower than limit of
minimum pressure (14-15).
OPBFT
High pressure
fault
Since feedback value of pump
pressure is lower than limit of
maximum flow.
Check feedback signal is
correct.
Check if feedback value of
pressure is lower than limit of
maximum pressure (14-12).
FBLSS
PID Feedback
Signal Loss
Since proportion of loss pressure
(14-19) is enabled and over high, the
inverter trips to fault. Thus, feedback
sensor cannot operate properly or is
not installed correctly
Check if the proportion of loss
pressure (14-19) is set correctly
Make sure the feedback sensor
is installed correctly and PID
feedback signal operates
normally.