4-28
Group 14 PUMP Application Function
No. Description Range
Factory
Setting
unit
Note
14-25
Period of Water Pressure
Detection
0.0~200.0 30.0 sec
Note1
14-26
Acceleration Time of Water
Pressure Detection
0.1~3600.0 12.0 sec
Note1
14-27
Deceleration Time of Water
Pressure Detection
0.1~3600.0 35.0 sec
Note1
14-28
Forced Run Command
0.00~(the value of 00-12) 0.00 Hz
Note1
14-29
Switching Time of Water
Pressure Detection
0~240 3 Hr
Note1
14-30
Detection Time of Multiple
Pumps in Parallel Running
Start
0~30.0 0.0 sec
Note1
14-31
Synchronous Selection of
Multiple Pumps in Parallel
0: Disable
1: Pressure Setting Run/Stop
2: Pressure Setting
3: Run/Stop
1 -
Note1
14-34
Tolerance Range of Constant
Pressure 2
When 14-20=0, range is 0.00~650.00
When 14-20=1, range is 0~100
5 PSI/%
Note1
14-35
Selection of Multiple Pumps
Shift Operation
0: No Function
1: Timer Alternately Selection
2: Sleep Stop Alternately Selection
3: Timer and Sleep Stop Alternately
Selection
4: Multiple Pumps Test Mode
1 -
Note1
14-37
Leakage Detection Time
0.0~100.0 0.0 sec
Note1
14-38
Pressure Variation of
Leakage Detection Restart
When 14-20=0, range is 0.00~65.00
When 14-20=1, range is 0~100
1 PSI/%
Note1
14-39
Pressure Tolerance Range of
Leakage Detection Restart
When 14-20=0, range is 0.00~650.00
When 14-20=1, range is 0~100
5 PSI/%
Note1
14-71
Maximum Pressure Setting 0.10~650.00
10 PSI
Note1
14-72
Switching Time of Alternation
in Parallel
0: Hour
1: Minute
0 -
Note1
14-73
Slave Wake-Up Selection
0: Disable
1: Enable
0 -
Note1
**(Group 14 can be used for PUMP application function built-in models only)