4-27
Group 14 PUMP Application Function
No. Description Range
Factory
Setting
unit
Note
14-00
Function Selection
0: Disable
1: PUMP
0 - Note1
14-01
Setting of Single & Multiple
Pumps and Master & Slave
Machines
0: Single Pump
1: Master
2: Slave 1
3: Slave 2
4: Slave 3
0 -
Note1
14-02
Operation Pressure Setting 0.1~(the value of 14-03) 4.00 PSI
Note1
14-03
Maximum Pressure Setting of
Pressure Transmitter
0.10 ~ 650.00
10.00 PSI
Note1
14-04
Pump Pressure Command
Source
0Set by 14-02
1Set by AI
0 -
Note1
14-05
Display Mode Selection
0: Display of Target and Pressure
Feedback (14-03<99)
1: Target Pressure Only
2: Feedback Pressure Only
0 -
Note1
14-06
Proportion Gain(P) 0.00~10.00
3.00 -
Note1
14-07
Integral Time(I) 0.0~100.0
0.5 sec
Note1
14-08
Differential Time(D) 0.00~10.00
0.00 sec
Note1
14-09
Tolerance Range of Constant
Pressure
When 14-20=0, range is 0.00~650.00
When 14-20=1, range is 0~100
5 PSI/%
Note1
14-10
Sleep Frequency of Constant
Pressure
0.00~599.00 30.00 Hz
Note1
14-11
Sleep Time of Constant
Pressure
0.0~255.5 0.0 sec
Note1
14-12
Maximum Pressure Limit
When 14-20=0, range is 0.00~650.00
When 14-20=1, range is 0~100
50 PSI/%
Note1
14-13
Warning Time of High
Pressure
0.0~600.0 10 sec
Note1
14-14
Stop Time of High Pressure
0.0~600.0 20 sec
Note1
14-15
Minimum Pressure Limit
When 14-20=0, range is 0.00~650.00
When 14-20=1, range is 0~100
5 PSI/%
Note1
14-16
Warning Time of Low
Pressure
0.0~600.0 0.0 sec
Note1
14-17
Fault Stop Time of Low
Pressure
0.0~600.0 0.0 sec
Note1
14-18
Time of Loss Pressure
Detection
0.0~600.0 0.0 sec
Note1
14-19
Proportion of Loss Pressure
Detection
0~100 0 %
Note1
14-20
Switching of Pressure and
Percentage
0: Pressure
1: Percentage
1 -
Note1
14-22
Slave Trip Frequency 0.00 ~ 599.00
45.00 Hz
Note1
14-23
Direction of Water Pressure
Detection
0: Upward Detection
1: Downward Detection
1 -
Note1
14-24
Range of Water Pressure
Detection
When 14-20=0, range is 0.00~650.00
When 14-20=1, range is 0~100
1 PSI/%
Note1