4-30
1. 00-02 or 00-03
2. 00-04
3. 03-00 to 03-04 as required. Not required for three wire control mode.
When 00-04=0
Two external switches are required, one for forward direction and the other for reverse.
Switch type: two position, maintained type. (This is two wire mode).
1. Forward (Run/Stop) Switch
Select one of the multifunction inputs [S1 to S5] and set the relevant parameter 03-00 to 03-04
= 0 (Forward run /Stop mode.)
2. Reverse (Run/Stop) Switch
Select one of the multifunction inputs [S1 to S5] and set the relevant parameter 03-00 to 03-04
= 1 (Reverse run /Stop mode.)
00-04 = 1
Two external switches are required.
Switch type: two position, maintained type. (This is two wire mode).
1. Run/Stop switch
Select one of the multifunction inputs [S1 to S5] and set the relevant parameter 03-00 to 03-04
= 0 (Run/Stop mode.)
2. Forward/Reverse Switch
Select one of the multifunction inputs [S1 to S5] and set the relevant parameter 03-00 to 03-04
= 1 (Forward/ Reverse direction selection.)
Switch in OFF position = Forward direction
Switch in ON
position = Reverse direction
00-04= 2. Three Wire Control mode Run/Stop
In this mode, two separated momentary push buttons are used for start and stop functions.
In this mode, parameter group 03 for S1 to S5 are not effective.
S1, S2 and S3 are allocated automatically.
Note: For S1 to initiate the Run command. Push button connected to S2 must be connected by
a normally closed type contact (NC).