4-88
Group 14 PUMP Application Function
14-00 Function Selection
Range
0: Disable
1: PUMP
Select function of pump via parameter 14-00. This function is enabled if PID control mode
(10-03) is enabled. Function of pump affects PID target value and if parameter group 14 are
enabled.
14-01 Setting of Single & Multiple Pumps and Master & Slave Machines
Range
0: Single Pump
1: Master
2: Slave 1
3: Slave 2
4: Slave 3
Set the inverter as the Master or Slave 1~3 via parameter 14-01. Refer chapter 3 for the functional
process of dual pump start to enable multiple pumps in parallel. It is required to
reconnect to write in the parameter after it is set.
14-02 Operation Pressure Setting
Range
0.1~(the value of 14-03)
Set the pressure value depending on the pressure transmitter of pump system after setting
10-00 to 0 (keypad given).
14-03 Maximum Pressure Setting of Pressure Transmitter
Range
0.1~650PSI
Set the maximum pressure value depending on the pressure transmitter of pump system. Parameter
23-02 is limited to this maximum value.
14-04 Pump Pressure Command Source
Range
0Set by 14-02
1Set by AI
Pressure command source is given the value set by 14-02 (Operation Pressure Setting) or AI.
Refer to parameter 10-00 for the setting of AI terminal.
)
14-05 Display Mode Selection
Range
0: Display of Target and Pressure Feedback (14-03<99)
1: Target Pressure Only
2: Feedback Pressure Only
This function can have the common display of target & feedback pressure or display separately
(1)
When 14-05=0, LED keypad displays pressure setting value and pressure feedback. Two-digit in
the left is the pressure value setting and two-digit in the right is the pressure feedback value in
the seven-segment monitor.