4-91
14-12 Maximum Pressure Limit
Range
When 14-20=0, range is 0.00~650.00
When 14-20=1, range is 0~100
It is convenient for user to limit maximum pressure. When pressure feedback value is higher than
maximum pressure limit, the inverter displays warning signal and then stops.
14-13 Warning Time of High Pressure
Range 0.0~600.0s
When pressure feedback value is higher than maximum pressure limit, warning time of high pressure
starts to count. If pressure feedback value is lower than maximum pressure limit during counting
time, the warning time will recount and the inverter will display the warning signal of HIPb when the
warning time ends.
14-14 Stop Time of High Pressure
Range 0.0~600.0s
When the warning signal of high pressure occurs and pressure feedback value is higher than
maximum pressure limit, stop time of high pressure starts to count. If pressure feedback value is
lower than maximum pressure limit during counting time, the stop time will recount and the inverter
will display stop error signal of OPbFt when the stop time ends.
14-15 Minimum Pressure Limit
Range
When 14-20=0, range is 0.00~650.00
When 14-20=1, range is 0~100
It is convenient for user to limit minimum pressure. When pressure feedback value is lower than
minimum pressure limit, the inverter displays warning signal and then stops.
Diagram for pressure feedback limit