4-93
When 14-20=0→1,
[(14-09)/(14-02)]x100% → 14-09=13% (Rounded to integer)
[(14-15)/(14-03)]x100% → 14-15=50% (Rounded to integer)
When 14-20=1→0,
[(14-09)/100]*(14-02) → 14-09=0.52PSI
[(14-15)/100]*(14-03) → 14-15=5.00PSI
14-22 Slave Trip Frequency
Range 【0.00~599.00】Hz
14-23 Direction of Water Pressure Detection
Range
0: Upward Detection
1: Downward Detection
14-24 Range of Water Pressure Detection
Range
When 14-20=0, range is 0.00~650.00
When 14-20=1, range is 0~100
14-25 Period of Water Pressure Detection
Range 【0.0~200.0】Hz
14-26 Acceleration Time of Water Pressure Detection
Range 【0.1~3600.0】s
14-27 Deceleration Time of Water Pressure Detection
Range 【0.1~3600.0】s
14-26 and 14-27 are corresponding to 00-16 and 00-17, so the setting of 23-26 changed with the
setting of 00-16. Thus, avoid using multi-speed application function while using PUMP function.
Diagram for upward detection of water pressure